Power Manager

Commercial power system inverter engineered for austere environments. Preconfigured and plug-and-play, it integrates grid, generator, and solar inputs to deliver efficient and resilient power conversion.

Mission Assurance

Key Features

UL 1741 Ed. 3, IEEE 1547, CSA 22.2 #107.1, IEEE 519, and CEC listed

Output

1.25 MW and 2.5 MW

DC Input

511–1500 VDC

AC Input

800 VAC Grid/Gen/DER

UL Certified

1741 Ed. 3

Protections

Multiple built-in

Optimized

Three-level topology

Ingress

NEMA 3R/IP 54

Warranty


10 Years

Technical Specifications

1.25 MW PowerManager

Physical Dimensions

  • Parameter: CPS-1250 Specification
  • Module Dimensions: 80 in x 49 in x 44 in
  • Weight: 1,980 lbs (898 kg)

Electrical Specifications

  • AC Input Voltage: 800, 690, 660, 630, 600, 540, 480, 415, 350 VAC
  • Grid Frequency: 60 Hz
  • Maximum Apparent Power: 1336 kVA (@800VAC) down to 585 kVA (@350VAC)
  • Maximum Real Power: 1336 kVA (@800VAC) down to 585 kVA (@350VAC)
  • Maximum AC Current: 964 ARMS
  • DC Voltage Range: 511-1500 VDC (@350-800 VAC)
  • Maximum DC Current: 1170 ADC
  • Power Factor: Four Quadrant
  • Maximum Efficiency: 98.5% (@1500 VDC), 98.7% (@1280 VDC)

Thermal Parameters & Protection

  • Operating Temperature: -30°C to +60°C, De-rated above +45°C
  • Cooling: Forced Air Cooled
  • Enclosure: NEMA 3R/IP 54
  • AC Breaker: Shunt Trip
  • Battery Protection: Voltage and Current Curtailment
  • Anti-Islanding Protection: Open Phase at Inverter Terminals
  • Voltage & Frequency Fault Protection: DC/AC Over/Under Voltage, Frequency, Current Faults
  • DC Input Protection: DC Input Fuses, DC Pre-Charge
  • Surge Protection: AC Surge Protection

System

  • Cooling: Forced Air Cooled
  • Enclosure: NEMA 3R/IP 54
  • Temperature Monitoring & Power Curtailment: Included

Technical Specifications

2.5 MW PowerManager

Thermal Parameters

  • Parameter: CPS-2500 Specification
  • Module Dimensions: 80 in x 85 in x 44 in
  • Weight: 3,970 lbs(1,800 kg)

Electrical Specifications

  • AC Input Voltage: 800, 690, 660, 630, 600, 540, 480, 415, 350 VAC
  • Grid Frequency: 60 Hz
  • Maximum Apparent Power: 2672 kVA (@800VAC) down to 1169 kVA (@350VAC)
  • Maximum Real Power: 2672 kW (@800VAC) down to 1169 kW (@350VAC)
  • Maximum AC Current: 1928 ARMS
  • DC Voltage Range: 511-1500 VDC (@350-800 VAC)
  • Maximum DC Current: 2340 ADC
  • Power Factor: Four Quadrant
  • Maximum Efficiency: 98.5% (@1500 VDC), 98.7% (@1280 VDC)

Thermal Parameters & Protection

  • Operating Temperature: -30°C to +60°C, De-rated above +45°C
  • Cooling: Forced Air Cooled
  • Enclosure: NEMA 3R/IP 54
  • AC Breaker: Shunt Trip
  • Battery Protection: Voltage and Current Curtailment
  • Anti-Islanding Protection: Open Phase at Inverter Terminals
  • Voltage & Frequency Fault Protection: DC/AC Over/Under Voltage, Frequency, Current Faults
  • DC Input Protection: DC Input Fuses, DC Pre-Charge
  • Surge Protection: AC Surge Protection

System

  • Cooling: Forced Air Cooled
  • Enclosure: NEMA 3R/IP 54
  • Temperature Monitoring & Power Curtailment: Included